NFPA 13 2019 8.3.1.2.1 Actuator Supervision
Have you ever walked into a Pre-Action Sprinkler System or Deluge Valve Sprinkler room and observed the “actuator” hanging loosely by, not connected to its proper valve actuator? This is a serious impairment of the system, as it will NOT operate upon detection as intended. Fear not, the NFPA 13 Technical Committee recognized that this is an important issue and resolved it with the requirement to monitor the actuator to ensure it is in place as required and the system will operate as intended if called upon.
NFPA 13 2019 8.3.1.2.1 Actuator Supervision. Effective January 1, 2021 removal of an electric actuator from the preaction or deluge valve that it controls shall result in an audible and visual indication of system impairment at the system releasing control panel.

January 14, 2025
For mechanical contractors, the busy season is a great opportunity to show customers that they can rely on you, but the increased workload creates a lot of stress for employees and customers, especially during a skilled labor shortage. Here we explore some innovative ways to balance the stress between supply and demand and optimize workflows […]

December 10, 2024
There are many HVAC and mechanical trade shows vying for your attention and attendance. And we know it would be great to attend them all as these events are so often valuable and invigorating—but we also know that’s not normally possible. Too many shows, too little time, and a limited budget! That’s why we’ve compiled […]